Phone:  (800) 908-7655 or (949) 768-5965   Fax: (949)768-5959



Considerations before purchasing/installing a new UPS

Single Phase UPS Systems

  • How long should the UPS run your load during a power outage, 10 minutes, 30 minutes, 60 minutes or more?
  • Can the UPS be plugged into your existing standard wall outlet or will you need an Electrician? UPS systems from 250 to 1500VA can be plugged into a standard 15 amp wall outlet. Larger systems require special outlets or twist lock receptacles.
  • Do you want the UPS to be rack mounted or to set on the floor?
  • Do you have enough rack or floor space for the UPS and Battery Cabinet?
  • What voltage does your load require? Some equipment requires standard 120Vac while others require 208, 230 or 240Vac.
  • Do you need built-in redundancy to minimize potential downtown?
  • Would you like a system that can grow with your needs?

Three Phase UPS Systems

  • How long should the UPS run your load during a power outage?
  • Do you have (or need) a backup generator?
  • What input and output voltages do you need? 120/208 or 480Vac?
  • Do you need a step down transformer for 480Vac to 120/208Vac?
  • Do you have the floor space for the UPS and battery cabinet (particularly for longer runtime systems greater than 15 minutes)?
  • Will your floor hold the weight of the UPS and Battery Cabinet without additional engineering and structural support?
  • Must the UPS be installed to comply with earthquake standards?
  • Do you need approval from your landlord to install the system into the building electrical circuits?
  • Will your elevator support the weight of the UPS and battery cabinet during installation?